Description
PR 4179B Universal trip amplifier is AC/DC Trip Amplifier with 2 relay outputs.
Functional highlights
- The 0… 5 AAC RMS range makes it possible to accurately measure a typical current transformer.
- The 0…300 VAC RMS range allows accurate supply voltage monitoring.
- The device measures standard input ranges and can be freely configured to customer-defined input range.
- Process control with 2 pairs of potential-free relay contacts which can be configured to suit any application.
- Trip amplifier with window function allowing the relay to change state within a high and a low setpoint on the input span.
- Simulation of process value during commissioning / maintenance.
- All terminals are over-voltage protected, polarity protected and short-circuit protected.
- The 4179B provides the required failure data (SFF and PFDAVG) for SIL 2 applications as per IEC 61508 / IEC 61511.
- Failure rates for 4179B correspond to Performance Level “d” according to ISO-13849.
- Accuracy < 0.3% of span.
- Temperature coefficient 0.01% / °C.
- Response time < 0.75 s for measuring AC current / voltage signals.
- High galvanic isolation of 2.3 kVAC.
- Extended EMC immunity: NAMUR NE21, A criterion, burst.
- Functional safety: HW assessment, SFF > 90%.
Programming – PR 4179B Universal trip amplifier
- Configuration, monitoring and diagnostics using PR 4500 detachable communication interfaces. Product-specific functionality includes communication via Modbus and Bluetooth using our PR Process Supervisor (PPS) application, available for iOS and Android.
- All programming can be password protected.
- Scrolling help text in 7 languages.
Mounting / installation
- Units can be mounted side by side, horizontally and vertically, without air gap on a standard DIN rail, even at 60°C ambient temperature.
Environmental Conditions for PR 4179B Universal trip amplifier
Operating temperature | -20°C to +60°C |
Storage temperature | -20°C to +85°C |
Calibration temperature | 20…28°C |
Relative humidity | < 95% RH (non-cond.) |
Protection degree | IP20 |
Installation in | Pollution degree 2 & meas. / overvoltage cat. II |
Mechanical specifications
Dimensions (HxWxD) | 109 x 23.5 x 104 mm |
Dimensions (HxWxD) w/ PR 4500 | 109 x 23.5 x 131 mm |
Weight approx. | 155 g |
DIN rail type | DIN EN 60715/35 mm |
Wire size | 0.13…2.08 mm2 AWG 26…14 stranded wire |
Screw terminal torque | 0.5 Nm |
Vibration | IEC 60068-2-6 |
2…13.2 Hz | ±1 mm |
13.2…100 Hz | ±0.7 g |
Common specifications
Supply voltage, universal | 21.6…253 VAC, 50…60 Hz or 19.2…300 VDC |
Internal fusible resistor | < 80 s, 2.4 A |
Max. required power | 1.2 W |
Max. power dissipation – current measurement | 2.2 W |
Max. power dissipation – voltage measurement | 1.2 W |
Test voltage | 2.3 kVAC |
Input to any (working) | 250 VAC (reinforced) |
Relay to relay (working) | 125 VAC (reinforced) |
Response time (0…90%, 100…10%) | < 0.75 s |
Signal dynamics, input | 20 bit |
Bandwidth | 40…400 Hz |
Programming | PR 4500 communication interfaces |
EMC immunity influence | < ±0.5% of span* |
Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% of span* |
of span | = of selected standard range |
Input specifications
Signal range | 0…5 AAC / 40…400 Hz |
Maximum input limit | 6.00 AAC @ 40°C |
Programmable measurement ranges | 0…0.5; 0…1; 0…2.5 & 0…5 AAC |
Custom configurable signal range | 0…5 AAC /40…400 Hz |
Min. measurement range (span) | 0.5 AAC |
Input resistance | < 0.042 Ω (incl. terminals) |
Signal range | 0…300 VAC / 40…400 Hz |
Programmable measurement ranges | 0…0.5, 0…1, 0…2.83, 0…5, 0…120, 0…230 & 0…300 VAC |
Custom configurable signal range | 0…300 VAC / 40…400 Hz |
Min. measurement range (span) | 0.5 VAC |
Input resistance | Nom. 3 MΩ || 100 pF |
Output specifications – PR 4179B Universal trip amplifier
Relay functions | Setpoint, Window, Error indication, Latch, Power and Off |
Hysteresis | 0…100% |
ON and OFF delay | 0…3600 s |
Power On delay | 0…9999 s |
Max. voltage | 250 VAC / VDC |
Max. current | 2 A |
Max. AC power | 500 VA |
Max. DC current, resistive load ≤ 30 VDC | 2 ADC |
Max. DC current, resistive load > 30 VDC | See manual for details |
Observed authority requirements
EMC | 2014/30/EU & UK SI 2016/1091 |
LVD | 2014/35/EU & UK SI 2016/1101 |
RoHS | 2011/65/EU & UK SI 2012/3032 |
Approvals
c UL us, UL 508 | E248256 |
SIL | Hardware assessed for use in SIL applications |
Data sheet