Description

PR 4179B Universal trip amplifier is AC/DC Trip Amplifier with 2 relay outputs.

Functional highlights

  • The 0… 5 AAC RMS range makes it possible to accurately measure a typical current transformer.
  • The 0…300 VAC RMS range allows accurate supply voltage monitoring.
  • The device measures standard input ranges and can be freely configured to customer-defined input range.
  • Process control with 2 pairs of potential-free relay contacts which can be configured to suit any application.
  • Trip amplifier with window function allowing the relay to change state within a high and a low setpoint on the input span.
  • Simulation of process value during commissioning / maintenance.
  • All terminals are over-voltage protected, polarity protected and short-circuit protected.
  • The 4179B provides the required failure data (SFF and PFDAVG) for SIL 2 applications as per IEC 61508 / IEC 61511.
  • Failure rates for 4179B correspond to Performance Level “d” according to ISO-13849.

Technical characteristics – PR 4179B Universal trip amplifier

  • Accuracy < 0.3% of span.
  • Temperature coefficient 0.01% / °C.
  • Response time < 0.75 s for measuring AC current / voltage signals.
  • High galvanic isolation of 2.3 kVAC.
  • Extended EMC immunity: NAMUR NE21, A criterion, burst.
  • Functional safety: HW assessment, SFF > 90%.

Programming – PR 4179B Universal trip amplifier

  • Configuration, monitoring and diagnostics using PR 4500 detachable communication interfaces. Product-specific functionality includes communication via Modbus and Bluetooth using our PR Process Supervisor (PPS) application, available for iOS and Android.
  • All programming can be password protected.
  • Scrolling help text in 7 languages.

Mounting / installation

  • Units can be mounted side by side, horizontally and vertically, without air gap on a standard DIN rail, even at 60°C ambient temperature.

Environmental Conditions for PR 4179B Universal trip amplifier

Operating temperature-20°C to +60°C
Storage temperature-20°C to +85°C
Calibration temperature20…28°C
Relative humidity< 95% RH (non-cond.)
Protection degreeIP20
Installation inPollution degree 2 & meas. / overvoltage cat. II

Mechanical specifications

Dimensions (HxWxD)109 x 23.5 x 104 mm
Dimensions (HxWxD) w/ PR 4500109 x 23.5 x 131 mm
Weight approx.155 g
DIN rail typeDIN EN 60715/35 mm
Wire size0.13…2.08 mm2 AWG 26…14 stranded wire
Screw terminal torque0.5 Nm
VibrationIEC 60068-2-6
2…13.2 Hz±1 mm
13.2…100 Hz±0.7 g

Common specifications

Supply

Supply voltage, universal21.6…253 VAC, 50…60 Hz or 19.2…300 VDC
Internal fusible resistor< 80 s, 2.4 A
Max. required power1.2 W
Max. power dissipation – current measurement2.2 W
Max. power dissipation – voltage measurement1.2 W

Isolation voltage

Test voltage2.3 kVAC
Input to any (working)250 VAC (reinforced)
Relay to relay (working)125 VAC (reinforced)

Response time

Response time (0…90%, 100…10%)< 0.75 s
Signal dynamics, input20 bit
Bandwidth40…400 Hz
ProgrammingPR 4500 communication interfaces
EMC immunity influence< ±0.5% of span*
Extended EMC immunity: NAMUR NE21, A criterion, burst< ±1% of span*
of span= of selected standard range

Input specifications

Current input

Signal range0…5 AAC / 40…400 Hz
Maximum input limit6.00 AAC @ 40°C
Programmable measurement ranges0…0.5; 0…1; 0…2.5 & 0…5 AAC
Custom configurable signal range0…5 AAC /40…400 Hz
Min. measurement range (span)0.5 AAC
Input resistance< 0.042 Ω (incl. terminals)

Voltage input

Signal range0…300 VAC / 40…400 Hz
Programmable measurement ranges0…0.5, 0…1, 0…2.83, 0…5, 0…120, 0…230 & 0…300 VAC
Custom configurable signal range0…300 VAC / 40…400 Hz
Min. measurement range (span)0.5 VAC
Input resistanceNom. 3 MΩ || 100 pF

Output specifications – PR 4179B Universal trip amplifier

Relay output

Relay functionsSetpoint, Window, Error indication, Latch, Power and Off
Hysteresis0…100%
ON and OFF delay0…3600 s
Power On delay0…9999 s
Max. voltage250 VAC / VDC
Max. current2 A
Max. AC power500 VA
Max. DC current, resistive load ≤ 30 VDC2 ADC
Max. DC current, resistive load > 30 VDCSee manual for details

Observed authority requirements

EMC2014/30/EU & UK SI 2016/1091
LVD2014/35/EU & UK SI 2016/1101
RoHS2011/65/EU & UK SI 2012/3032

Approvals

c UL us, UL 508E248256
SILHardware assessed for use in SIL applications
Data sheet

Additional information

Input

AC Current, AC Voltage

Output

2xRelays

Power Supply

Universal

Function

Trip Amplifier

Advanced Features

Process Calibration, Simulation, Display Scaling, Front Configuration with Detachable Display 4510, 4511, 4512, Data Logging using 4512 Bluetooth Communication Enabler/Configurator, Password Protection

You may also like…

PR 2231 Trip Amplifier

$363$404

Fast Delivery
PR 4131 Universal Trip Amplifier

$210

6 Sold 1 in stock