Applications of 4116 Universal Transmitter / Temperature Transmitter
- Linearized, electronic temperature measurement with RTD or TC sensor.
- Conversion of linear resistance variation to a standard analog current/voltage signal, i.e. from solenoids and butterfly valves or linear movements with attached potentiometer.
- Power supply and signal isolator for 2-wire transmitters.
- Process control with 2 pairs of potential-free relay contacts and analog output.
- Galvanic separation of analog signals and measurement of floating signals.
- The 4116 is designed according to strict safety requirements and is therefore suitable for application in SIL 2 installations.
- Suitable for use in systems up to Performance Level “d” according to ISO-13849.
Technical characteristics of Universal Transmitter PR 4116
- When PR4116 Universal Transmitter / Temperature Transmitter is used in combination with the PR 4500 display series, all operational parameters can be modified to suit any application. As the PR4116 transmitter is designed with electronic hardware switches, it is not necessary to open the device for setting of DIP-switches.
- A green / red front LED indicates normal operation and malfunction. A yellow LED is ON for each active output relay.
- Continuous check of vital stored data for safety reasons.
- 4-port 2.3 kVAC galvanic isolation.
Mounting / installation / programming
- Very low power consumption means units can be mounted side by side without an air gap – even at 60°C ambient temperature.
- Configuration, monitoring, 2-point process calibration and more are accomplished using PR’s 4500 series of detachable displays.
- All programming can be password-protected for PR 4116 Universal Transmitter / Temperature Transmitter.
Official Product Details
If you have any other questions about 4116 Universal Transmitter / Temperature Transmitter or the PR 4116 price, please contact us.
PR Electronics PR 4116 – Datasheet
Environmental Conditions
Operating temperature | -20°C to +60°C |
Storage temperature | -20°C to +85°C |
Calibration temperature | 20…28°C |
Relative humidity | < 95% RH (non-cond.) |
Protection degree | IP20 |
Mechanical specifications – PR 4116 transmitter
Dimensions (HxWxD) | 109 x 23.5 x 104 mm |
Dimensions (HxWxD) w/ PR 4500 | 109 x 23.5 x 131 mm |
Weight approx. | 175 g |
Weight incl. 4501 / 451x (approx.) | 190 g / 205 g |
Wire size | 0.13…2.08 mm2 AWG 26…14 stranded wire |
Screw terminal torque | 0.5 Nm |
Vibration | IEC 60068-2-6 |
2…13.2 Hz | ±1 mm |
13.2…100 Hz | ±0.7 g |
Common specifications
Supply voltage, universal | 21.6…253 VAC, 50…60 Hz or 19.2…300 VDC |
Fuse | 400 mA SB / 250 VAC |
Max. required power | ≤ 2.5 W |
Max. power dissipation | ≤ 2.5 W |
Test voltage | 2.3 kVAC |
Working voltage | 250 VAC (reinforced) / 500 VAC (basic) |
Temperature input (0…90%, 100…10%) | ≤ 1 s |
mA / V input (0…90%, 100…10%) | ≤ 400 ms |
2-w. supply (term. 44…43) | 25…16 VDC / 0…20 mA |
Programming | PR 4500 communication interfaces |
Signal dynamics, input | 24 bit |
Signal dynamics, output | 16 bit |
Signal / noise ratio | Min. 60 dB (0…100 kHz) |
Accuracy | Better than 0.1% of sel. range |
EMC immunity influence | < ±0.5% of span |
Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% of span |
Input specifications
RTD type | Pt10/20/50/100/200/250; Pt300/400/500/1000; Ni50/100/120/1000; Cu10/20/50/100 |
Cable resistance per wire | 50 Ω (max.) |
Sensor current | Nom. 0.2 mA |
Effect of sensor cable resistance (3-/4-wire) | < 0.002 Ω / Ω |
Sensor error detection | Yes |
Short circuit detection | < 15 Ω |
Linear resistance min….max. | 0 Ω…10000 Ω |
Potentiometer min….max. | 10 Ω…100 kΩ |
Thermocouple type | B, E, J, K, L, N, R, S, T, U, W3, W5, LR |
Cold junction compensation (CJC) via ext. sensor in 5910 | 20…28°C ≤ ±1°C, -20…20°C / 28…70°C ≤ 2°C |
CJC via int. mounted sensor | ±(2.0°C + 0.4°C * Δt) |
Sensor error detection | Yes |
Sensor error current: When detecting / else | Nom. 2 μA / 0 μA |
Measurement range | 0…23 mA |
Programmable measurement ranges | 0…20 and 4…20 mA |
Input resistance | Nom. 20 Ω + PTC 50 Ω |
Sensor error detection: Loop break 4…20 mA | Yes |
Measurement range | 0…12 VDC |
Programmable measurement ranges | 0/0.2…1, 0/1…5, 0/2…10 VDC |
Input resistance | Nom. 10 MΩ |