Description
Advanced features of PR 9106B HART transparent repeater
- The PR 45xx detachable display and the green and red front LEDs indicate operation status for each channel of 9106B – HART transparent repeater ATEX Approved IS Barrier.
- Monitoring of error events and cable breakage on input via the individual status relay and/or a collective electronic signal via the power rail.
- Suitable for the use in systems up to Performance Level “d” according to ISO-13849.
Technical characteristics – PR 9106B HART transparent repeater
- High galvanic isolation of 2.6 kVAC.
- Fast response time <5 ms
- High accuracy better than 0.1%.
- 2-wire transmitter supply >16 V.
Mounting – PR 9106B HART transparent repeater
- The devices can be mounted vertically or horizontally without distance between neighboring units.
Environmental Conditions
Operating temperature | -20°C to +60°C |
Storage temperature | -20°C to +85°C |
Calibration temperature | 20…28°C |
Relative humidity | < 95% RH (non-cond.) |
Protection degree | IP20 |
Installation in | Pollution degree 2 & meas. / overvoltage cat. II |
Mechanical specifications
Dimensions (HxWxD) | 109 x 23.5 x 104 mm |
Dimensions (HxWxD) w/ PR 4500 | 109 x 23.5 x 131 mm |
Weight approx. | 250 g |
DIN rail type | DIN EN 60715/35 mm |
Wire size | 0.13…2.08 mm2 AWG 26…14 stranded wire |
Screw terminal torque | 0.5 Nm |
Vibration | IEC 60068-2-6 |
2…13.2 Hz | ±1 mm |
13.2…100 Hz | ±0.7 g |
Common specifications
Supply | |
Supply voltage | 19.2…31.2 VDC |
Fuse | 1.25 A SB / 250 VAC |
Max. required power | ≤ 1.1 W / ≤ 1.9 W (1 ch. / 2 ch.) |
Max. power dissipation, 1 / 2 ch. | ≤ 0.8 W / ≤ 1.2 W |
Isolation voltage | |
Test /working: Input to any | 2.6 kVAC / 300 VAC reinforced isolation |
Analog output to supply | 2.6 kVAC / 300 VAC reinforced isolation |
Status relay to supply | 1.5 kVAC / 150 VAC reinforced isolation |
Response time | |
Response time (0…90%, 100…10%) | < 5 ms |
Programming | PR 4500 communication interfaces |
Signal dynamics, input | Analog signal chain |
Signal dynamics, output | Analog signal chain |
SMART bi-directional communication frequency range | 0.5…7.5 kHz |
Signal / noise ratio | > 60 dB |
Accuracy | Better than 0.1% of sel. range |
mA, absolute accuracy | ≤ ±16 μA |
mA, temperature coefficient | ≤ ±1.6 μA / °C |
Effect of supply voltage change on output (nom. 24 VDC) | < ±10 μA |
EMC immunity influence | < ±0.5% of span |
Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% of span |
Input specifications – PR 9106B HART transparent repeater
Current input | |
Measurement range | 3.5…23 mA |
2-wire transmitter supply 9106B1x (Uo = 27.5 VDC) | >16 V / 20 mA |
2-wire transmitter supply 9106B2x (Uo = 25.3 VDC) | >15 V / 20 mA |
Sensor error detection: Loop break 4…20 mA | < 1 mA |
Input voltage drop, supplied unit | < 4 V @ 23 mA |
Input voltage drop, non-supplied unit | < 6 V @ 23 mA |
Output specifications – PR 9106B HART transparent repeater
Current output | |
Signal range | 3.5…23 mA |
Load (@ current output) | ≤ 600 Ω |
Load stability | ≤ 0.01% of span / 100 Ω |
Current limit | ≤ 28 mA |
Passive 2-wire mA output | |
Effect of external 2-wire supply voltage variation | < 0.005% of span / V |
Max. external 2-wire supply | 26 VDC |
Status relay | |
Relay function | N.C. |
Programmable low setpoint | 0…29.9 mA |
Programmable high setpoint | 0…29.9 mA |
Hysteresis for setpoints | 0.1 mA |
Max. voltage | 125 VAC / 110 VDC |
Max. current | 0.5 AAC / 0.3 ADC |
Max. voltage – hazardous installation | 32 VDC / 32 VAC |
Max. current – hazardous installation | 1 ADC / 0.5 AAC |
of span | = normal measurement range 4…20 mA |
Observed authority requirements
EMC | 2014/30/EU & UK SI 2016/1091 |
LVD | 2014/35/EU & UK SI 2016/1101 |
ATEX | 2014/34/EU & UK SI 2016/1107 |
RoHS | 2011/65/EU & UK SI 2012/3032 |
EAC | TR-CU 020/2011 |
EAC Ex | TR-CU 012/2011 |
EAC LVD | TR-CU 004/2011 |