Description

Advanced features  of PR 9106B HART transparent repeater

  • The PR 45xx detachable display and the green and red front LEDs indicate operation status for each channel of 9106B – HART transparent repeater ATEX Approved IS Barrier.
  • Monitoring of error events and cable breakage on input via the individual status relay and/or a collective electronic signal via the power rail.
  • Suitable for the use in systems up to Performance Level “d” according to ISO-13849.

Technical characteristics – PR 9106B HART transparent repeater

  • High galvanic isolation of 2.6 kVAC.
  • Fast response time <5 ms
  • High accuracy better than 0.1%.
  • 2-wire transmitter supply >16 V.

Mounting – PR 9106B HART transparent repeater

  • The devices can be mounted vertically or horizontally without distance between neighboring units.

Environmental Conditions

Operating temperature-20°C to +60°C
Storage temperature-20°C to +85°C
Calibration temperature20…28°C
Relative humidity< 95% RH (non-cond.)
Protection degreeIP20
Installation inPollution degree 2 & meas. / overvoltage cat. II

Mechanical specifications

Dimensions (HxWxD)109 x 23.5 x 104 mm
Dimensions (HxWxD) w/ PR 4500109 x 23.5 x 131 mm
Weight approx.250 g
DIN rail typeDIN EN 60715/35 mm
Wire size0.13…2.08 mm2 AWG 26…14 stranded wire
Screw terminal torque0.5 Nm
VibrationIEC 60068-2-6
2…13.2 Hz±1 mm
13.2…100 Hz±0.7 g

Common specifications

Supply

Supply voltage19.2…31.2 VDC
Fuse1.25 A SB / 250 VAC
Max. required power≤ 1.1 W / ≤ 1.9 W (1 ch. / 2 ch.)
Max. power dissipation, 1 / 2 ch.≤ 0.8 W / ≤ 1.2 W

Isolation voltage

Test /working: Input to any2.6 kVAC / 300 VAC reinforced isolation
Analog output to supply2.6 kVAC / 300 VAC reinforced isolation
Status relay to supply1.5 kVAC / 150 VAC reinforced isolation

Response time

Response time (0…90%, 100…10%)< 5 ms
ProgrammingPR 4500 communication interfaces
Signal dynamics, inputAnalog signal chain
Signal dynamics, outputAnalog signal chain
SMART bi-directional communication frequency range0.5…7.5 kHz
Signal / noise ratio> 60 dB
AccuracyBetter than 0.1% of sel. range
mA, absolute accuracy≤ ±16 μA
mA, temperature coefficient≤ ±1.6 μA / °C
Effect of supply voltage change on output (nom. 24 VDC)< ±10 μA
EMC immunity influence< ±0.5% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst< ±1% of span

Input specifications – PR 9106B HART transparent repeater

Current input

Measurement range3.5…23 mA
2-wire transmitter supply 9106B1x (Uo = 27.5 VDC)>16 V / 20 mA
2-wire transmitter supply 9106B2x (Uo = 25.3 VDC)>15 V / 20 mA
Sensor error detection: Loop break 4…20 mA< 1 mA
Input voltage drop, supplied unit< 4 V @ 23 mA
Input voltage drop, non-supplied unit< 6 V @ 23 mA

Output specifications – PR 9106B HART transparent repeater

Current output

Signal range3.5…23 mA
Load (@ current output)≤ 600 Ω
Load stability≤ 0.01% of span / 100 Ω
Current limit≤ 28 mA

Passive 2-wire mA output

Effect of external 2-wire supply voltage variation< 0.005% of span / V
Max. external 2-wire supply26 VDC

Status relay

Relay functionN.C.
Programmable low setpoint0…29.9 mA
Programmable high setpoint0…29.9 mA
Hysteresis for setpoints0.1 mA
Max. voltage125 VAC / 110 VDC
Max. current0.5 AAC / 0.3 ADC
Max. voltage – hazardous installation32 VDC / 32 VAC
Max. current – hazardous installation1 ADC / 0.5 AAC
of span= normal measurement range 4…20 mA

Observed authority requirements

EMC2014/30/EU & UK SI 2016/1091
LVD2014/35/EU & UK SI 2016/1101
ATEX2014/34/EU & UK SI 2016/1107
RoHS2011/65/EU & UK SI 2012/3032
EACTR-CU 020/2011
EAC ExTR-CU 012/2011
EAC LVDTR-CU 004/2011

Data sheet & Manuals

Additional information

Weight1.5 kg
Version

1:Uo = 28V, 2: Uo = 25.6V