Description

Applications

PR 6437D HART 7 Temperature Transmitter – PR Electronics

  • Temperature measurement of a wide range of TC and RTD types.
  • Conversion of wide span linear resistance and potentiometer inputs to 4…20 mA.
  • Conversion of bipolar mV signals to 4…20 mA.
  • Integration into asset management schemes.
  • Critical applications requiring superior accuracy and/or sensor redundancy and drift detection.

Technical characteristics

  • True dual input transmitter, accepts the widest range of dual input combinations.
  • Sensor redundancy – output automatically switches to secondary sensor in event of primary sensor failure, maintaining uptime.
  • Sensor drift detection – alerts when sensor differential exceeds user-defined limits, for maintenance optimization.
  • Dynamic variable mapping for process data in addition to the primary variable e.g. dual input features such as average, differential and min./max. tracking.
  • Groundbreaking digital and analog signal accuracy over full input span and ambient conditions.
  • Extensive sensor matching including Callendar Van Dusen and custom linearizations.
  • Programmable input limits with runtime metering ensure maximum process traceability and sensor out of range protection.
  • IEC 61508 : 2010 full assessment up to SIL 3 together with enhanced EMC Functional Safety testing to IEC 61236-3-1.
  • 6437xxSx is suitable for the use in systems up to Performance Level “d” according to ISO-13849
  • Meets NAMUR NE21, NE43, NE44, NE89 and NE107 compliant diagnostics information.

Mounting / installation / programming

  • DIN rail mounting with up to 84 inputs per meter.
  • Configuration via PReset using PR5909 Loop Link / HART modem, or by Asset Management tool (e.g. Pactware, AMS, HART communicator).
  • The 6437D can be mounted in zone 0, 1, 2 and zone 21, 22 including M1 / Class I, Division 1, Groups A, B, C, D.

Data sheet & Manuals


Data sheet

Manuals

Environmental Conditions

Operating temperature-50°C to +85°C (standard) -40°C to +80°C (SIL)
Storage temperature-50°C to +85°C
Calibration temperature23…25°C
Relative humidity< 99% RH (non-cond.)
Protection degreeIP20

Mechanical specifications

Dimensions (HxWxD)109 x 23.5 x 104 mm
Weight (single input / dual input)150 g / 160 g
Wire size0.13…2.08 mm2 AWG 26…14 stranded wire
DIN rail typeDIN EN 60715/35 mm
Screw terminal torque0.5 Nm
VibrationIEC 60068-2-6
2…25 Hz±1.6 mm
25…100 Hz±4 g

Common specifications

Supply

Supply voltage7.5*…30** VDC
Power dissipation, per channel≤ 850 mW
Additional min. supply voltage when using test terminals0.8 V
Min. load resistance at >37 V supply(Vsupply – 37) / 23 mA

Isolation voltage

Isolation voltage, test / working2.5 kVAC / 42 VAC

Response time

Response time75 ms
Programmable damping0…60 s
Polarity protectionAll inputs and outputs
Warm-up time< 5 min.
Start-up time< 2.75 s
ProgrammingLoop Link & HART
Write protectionJumper or software
Signal / noise ratio> 60 dB
Long-term stability, better than±0.05% of span / year (±0.18% of span / 5 years)
Signal dynamics, input24 bit
Signal dynamics, output18 bit
Effect of supply voltage change< 0.005% of span / VDC
AccuracySee manual for details
EMC immunity influence< ±0.1% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst< ±1%

Input specifications

RTD input

RTD typePt10…10000, Ni10…10000, Cu5…1000
Basic accuracy, e.g. Pt100≤ ±0.04°C
Cable resistance per wire50 Ω (max.)
Effect of sensor cable resistance (3-/4-wire)< 0.002 Ω / Ω
Sensor current< 0.15 mA
Sensor error detectionNone, Shorted, Broken, Shorted or Broken

TC input

Thermocouple typeB, E, J, K, L, N, R, S, T, U, W3, W5, LR
Basic accuracy, e.g. TC K≤ ±0.25°C
Cold junction compensation (CJC)Constant, internal or external via a Pt100 or Ni100 sensor
Sensor error detectionNone, Shorted, Broken, Shorted or Broken

Linear resistance input

Measurement range / min. range (span)0 Ω…100 kΩ / 25 Ω
Cable resistance per wire (max.)50 Ω
Sensor current< 0.15 mA
Sensor error detectionNone, Broken

Potentiometer input

Potentiometer min….max.10 Ω…100 kΩ
Measurement range / min. range (span)0…100% / 10%
Cable resistance per wire (max.)50 Ω
Sensor current< 0.15 mA
Sensor error detectionNone, Shorted, Broken, Shorted or Broken

mV input

Measurement range-800…+800 mV (bipolar) -100…1700 mV
Min. measurement range (span)2.5 mV
Input resistance10 MΩ
Sensor error detectionNone, Broken

Output specifications

Common output specifications

Normal range, programmable3.8…20.5 / 20.5…3.8 mA
Extended range (output limits), programmable3.5…23 / 23…3.5 mA
Basic accuracy≤ ±1.6 μA (0.01% of full output span)
Updating time10 ms
Load (@ current output)≤ (Vsupply -7.5)/0.023 [Ω]
Load stability< 0.01% of span / 100 Ω
Sensor error indicationProgrammable 3.5…23 mA
NAMUR NE 43 Upscale/Downscale> 21 mA / < 3.6 mA
HART protocol revisionsHART 7 and HART 5

Observed authority requirements

EMC2014/30/EU & UK SI 2016/1091
ATEX2014/34/EU & UK SI 2016/1107
RoHS2011/65/EU & UK SI 2012/3032
EACTR-CU 020/2011
EAC ExTR-CU 012/2011

Approvals

ATEXDEKRA 16ATEX0047X
IECExIECEx DEK. 16.0029X
CSACSA 16.70066266
c FM usFM16US0287X / FM16CA0146X
INMETRODEKRA 23.0002X
NEPSIGYJ23.1253X
EAC ExEAEU KZ 7500361.01.01.08756
EU RO MR Type ApprovalMRA0000023
SILSIL 2 / SIL 3 certified & fully assessed acc. to IEC 61508

Enhance Your Temperature Measurement with PR Electronics

The PR 6437D HART 7 Transmitter by PR Electronics delivers high-precision temperature measurements with enhanced digital communication. Designed for industrial applications, this transmitter ensures reliability, accuracy, and seamless integration into control systems.

Key Features and Benefits

  • HART 7 Protocol Compatibility – Advanced diagnostics, remote configuration, and improved response times.
  • High Accuracy & Stability – Precise temperature measurements with minimal drift over time.
  • Universal Sensor Input – Supports RTDs, thermocouples, and resistance/voltage inputs.
  • Loop-Powered (2-Wire Design) – Reduces wiring complexity and enhances energy efficiency.
  • Robust Industrial Design – Operates in harsh environments with high resistance to electrical noise and extreme temperatures.

Why Choose PR Electronics?

PR Electronics is a leader in industrial signal conditioning, offering innovative temperature transmitters with superior performance. The PR 6437D Transmitter is engineered for optimal integration into modern process automation systems, making it an ideal choice for industries like oil & gas, chemical processing, and manufacturing.

Applications

  • Process Automation
  • Power Generation
  • Food & Beverage
  • Chemical & Pharmaceutical Industries
  • HVAC & Environmental Monitoring

Get Started Today

Upgrade your temperature monitoring with the PR 6437D HART 7 Transmitter. Contact us today for more information or a customized solution tailored to your industry needs.

 

Additional information

Input

Universal

Output

HART, Current

Power Supply

2-Wire Loop

Function

Temperature, Transmitter

Mounting Type

DIN Rail

Make

PR Electronics

Origin

Denmark

Warranty

5 Years

Related Products

PR 3101 TC converter

$125

1 in stock
Fast Delivery
PR 3331 Temperature Converter

$147

1 in stock
Fast Delivery
PR 3105 Isolated converter

$159

1 in stock
Fast Delivery