Description

PR 4131 Universal Trip Amplifier with 2 relay outputs.

Advanced features

  • Programmable via detachable display front (PR 4500 series), process calibration, relay simulation, password protection, error diagnostics and selection of help text in several languages.

Application – 4131 Universal Trip Amplifier

  • Process control with 2 pairs of potential-free relay contacts which can be configured to suit any application.
  • Trip amplifier with window function defined by a high and a low setpoint. The relay changes state outside the window.
  • Relay latch function, where the relay is activated and can only be reset manually.
  • Sophisticated sensor error surveillance, where one relay holds the state immediately prior to the sensor error, while allowing the process to continue. The other relay can be set for sensor error alarm so that the defect sensor can be replaced immediately.

Technical characteristics

  • When the universal trip amplifier 4131 is used with the PR 4500 display series, all operational parameters can be modified to suit any application. As the pr 4131 universal transmitter is designed with electronic hardware switches, it is not necessary to open the device for setting of DIP-switches.
  • A green front LED indicates normal operation and malfunction. A yellow LED is ON for each active output relay.
  • Continuous check of vital stored data for safety reasons.
  • 3-port 2.3 kVAC galvanic isolation.

Popular Uses – PR Electronics 4131

  • mA Trip Amplifier
  • Temperature Safety Relay
  • Trip Protection Switch
  • Level Controller with relays
  • Engine Temperature Safety relay / Temperature Trip Amplifier

Product Datasheet

Environmental Conditions

Operating temperature-20°C to +60°C
Calibration temperature20…28°C
Relative humidity< 95% RH (non-cond.)
Protection degreeIP20

Mechanical specifications

Dimensions (HxWxD)109 x 23.5 x 104 mm
Dimensions (HxWxD) w/ PR 4500109 x 23.5 x 131 mm
Weight approx.170 g
Weight incl. 4501 / 451x (approx.)185 g / 200 g
Wire size0.13…2.08 mm2 AWG 26…14 stranded wire
Screw terminal torque0.5 Nm
VibrationIEC 60068-2-6
2…13.2 Hz±1 mm
13.2…100 Hz±0.7 g

Common specifications

Supply

Supply voltage, universal21.6…253 VAC, 50…60 Hz or 19.2…300 VDC
Fuse400 mA SB / 250 VAC
Max. required power≤ 2.0 W
Max. power dissipation≤ 2.0 W

Isolation voltage

Isolation voltage, test / working2.3 kVAC / 250 VAC

Response time – PR4131

Temperature input (0…90%, 100…10%)≤ 1 s
mA / V input (0…90%, 100…10%)≤ 400 ms

Auxiliary supplies

2-w. supply (term. 44…43)25…16 VDC / 0…20 mA
ProgrammingPR 4500 communication interfaces
Signal / noise ratioMin. 60 dB (0…100 kHz)
AccuracyBetter than 0.1% of sel. range
EMC immunity influence< ±0.5% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst< ±1% of span

Input specifications – PR 4131 Universal Trip Amplifier

RTD input

RTD typePt10/20/50/100/200/250; Pt300/400/500/1000; Ni50/100/120/1000; Cu10/20/50/100
Cable resistance per wire50 Ω (max.)
Sensor currentNom. 0.2 mA
Effect of sensor cable resistance (3-/4-wire)< 0.002 Ω / Ω
Sensor error detectionYes
Short circuit detection< 15 Ω

Linear resistance input

Linear resistance min….max.0 Ω…10000 Ω

Potentiometer input

Potentiometer min….max.10 Ω…100 kΩ

TC input

Thermocouple typeB, E, J, K, L, N, R, S, T, U, W3, W5, LR
Cold junction compensation (CJC) via ext. sensor in 591020…28°C ≤ ±1°C, -20…20°C / 28…70°C ≤ 2°C
CJC via int. mounted sensor±(2.0°C + 0.4°C * Δt)
Sensor error detectionYes
Sensor error current: When detecting / elseNom. 2 μA / 0 μA

Current input

Measurement range0…23 mA
Programmable measurement ranges0…20 and 4…20 mA
Input resistanceNom. 20 Ω + PTC 50 Ω

Voltage input

Measurement range0…12 VDC
Programmable measurement ranges0/0.2…1, 0/1…5, 0/2…10 VDC
Input resistanceNom. 10 MΩ

Output specifications – PR 4131 Universal Trip Amplifier

Relay output

Relay functionsSetpoint, Window, Sensor error, Latch, Power and Off
Hysteresis0…100%
ON and OFF delay0…3600 s
Max. voltage250 VRMS
Max. current2 AAC or 1 ADC
Max. AC power500 VA
Sensor error reactionBreak / Make / Hold
of span= of the presently selected range

Observed authority requirements

EMC2014/30/EU & UK SI 2016/1091
LVD2014/35/EU & UK SI 2016/1101
RoHS2011/65/EU & UK SI 2012/3032
EACTR-CU 020/2011
EAC LVDTR-CU 004/2011

Approvals – PR 4131 Universal Trip Amplifier

c UL us, UL 508E231911
FM3025177
DNV MarineTAA0000101
EU RO MR Type ApprovalMRA000000Z

Additional information

Input

Universal

Output

2xRelays

Power Supply

Universal

Function

Signal Converter, Universal Transmitter, Universal Converter, Safety Relay, Temperature Trip Amplifier, Trip Amplifier

Mounting Type

DIN Rail

Make

PR Electronics

Origin

Denmark

Warranty

5 Years

Applications

Process Trip Amplifier, Temperature Safety Relay, Trip Protection Switch, Level Controller with relays, Engine Temperature Safety relay, Temperature Trip Amplifier, and many more

You may also like…

4116 Universal transmitter Peters SL - 4116 G3 Universal transmitter Peters SL 1307 PR Electronics buy from topline smart systems
-7%
PR 4116 Universal Transmitter

$246 Original price was: $246.$229Current price is: $229.

18 Sold
Fast Delivery
PR 2231 Trip Amplifier

$363$404

Fast Delivery