Description
PR 4114 Universal Transmitter accepts universal input and gives mA/V output.
Advanced features
- Programmable by way of detachable display front (PR 4500 series), process calibration, signal simulation, password protection, error diagnostics and help text available in several languages.
Application – 4114 Universal Transmitter
- Linearized, electronic temperature measurement with RTD or TC sensor.
- Conversion of linear resistance variation to a standard analog current / voltage signal, i.e. from solenoids and butterfly valves or linear movements with attached potentiometer.
- Power supply and signal isolator for 2-wire transmitters.
- Process control with standard analog output.
- Galvanic separation of analog signals and measurement of floating signals.
- The 4114 is designed according to strict safety requirements and is therefore suitable for application in SIL 2 installations.
- Suitable for the use in systems up to Performance Level “d” according to ISO-13849.
Technical characteristics
- When 4114 is used with the PR 4500 display series, all operational parameters can be modified to suit any application. As the 4114 is designed with electronic hardware switches, it is not necessary to open the device for setting of DIP-switches.
- A green / red front LED indicates normal operation and malfunction.
- Continuous check of vital stored data for safety reasons.
- 3-port 2.3 kVAC galvanic isolation.
Data sheet PR 4114 – PR Electronics
Environmental Conditions
Operating temperature | -20°C to +60°C |
Storage temperature | -20°C to +85°C |
Calibration temperature | 20…28°C |
Relative humidity | < 95% RH (non-cond.) |
Protection degree | IP20 |
Mechanical specifications
Dimensions (HxWxD) | 109 x 23.5 x 104 mm |
Weight approx. | 155 g |
Weight incl. 4501 / 451x (approx.) | 170 g / 185 g |
Wire size | 0.13…2.08 mm2 AWG 26…14 stranded wire |
Screw terminal torque | 0.5 Nm |
Vibration | IEC 60068-2-6 |
2…13.2 Hz | ±1 mm |
13.2…100 Hz | ±0.7 g |
Common specifications – PR 4114 Universal Transmitter
Supply voltage, universal | 21.6…253 VAC, 50…60 Hz or 19.2…300 VDC |
Fuse | 400 mA SB / 250 VAC |
Max. required power | ≤ 2.0 W |
Max. power dissipation | ≤ 2.0 W |
Isolation voltage, test / working | 2.3 kVAC / 250 VAC |
Temperature input (0…90%, 100…10%) | ≤ 1 s |
mA / V input (0…90%, 100…10%) | ≤ 400 ms |
2-w. supply (term. 44…43) | 25…16 VDC / 0…20 mA |
Programming | PR 4500 communication interfaces |
Signal / noise ratio | Min. 60 dB (0…100 kHz) |
Accuracy | Better than 0.1% of sel. range |
EMC immunity influence | < ±0.5% of span |
Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% of span |
Input specifications – PR 4114 Universal Transmitter
RTD type | Pt10/20/50/100/200/250; Pt300/400/500/1000; Ni50/100/120/1000; Cu10/20/50/100 |
Cable resistance per wire | 50 Ω (max.) |
Sensor current | Nom. 0.2 mA |
Effect of sensor cable resistance (3-/4-wire) | < 0.002 Ω / Ω |
Sensor error detection | Yes |
Short circuit detection | < 15 Ω |
Linear resistance min….max. | 0 Ω…10000 Ω |
Potentiometer min….max. | 10 Ω…100 kΩ |
Thermocouple type | B, E, J, K, L, N, R, S, T, U, W3, W5, LR |
Cold junction compensation (CJC) via ext. sensor in 5910 | 20…28°C ≤ ±1°C, -20…20°C / 28…70°C ≤ 2°C |
CJC via int. mounted sensor | ±(2.0°C + 0.4°C * Δt) |
Sensor error detection | Yes |
Sensor error current: When detecting / else | Nom. 2 μA / 0 μA |
Measurement range | 0…23 mA |
Programmable measurement ranges | 0…20 and 4…20 mA |
Input resistance | Nom. 20 Ω + PTC 50 Ω |
Sensor error detection: Loop break 4…20 mA | Yes |
Measurement range | 0…12 VDC |
Programmable measurement ranges | 0/0.2…1, 0/1…5, 0/2…10 VDC |
Input resistance | Nom. 10 MΩ |
Output specifications – PR Electronics 4114 Universal Transmitter
Signal range | 0…23 mA |
Programmable signal ranges | 0…20/4…20/20…0/20…4 mA |
Load (@ current output) | ≤ 800 Ω |
Load stability | ≤ 0.01% of span / 100 Ω |
Sensor error indication | 0 / 3.5 / 23 mA / none |
NAMUR NE43 Upscale/Downscale | 23 mA / 3.5 mA |
Output limitation, on 4…20 and 20…4 mA signals | 3.8…20.5 mA |
Output limitation, on 0…20 and 20…0 mA signals | 0…20.5 mA |
Current limit | ≤ 28 mA |
Signal range | 0…10 VDC |
Programmable signal ranges | 0/0.2…1; 0/1…5 ; 0/2…10; 1…0.2/0; 5…1/0; 10…2/0 V |
Load (@ voltage output) | ≥ 500 kΩ |
of span | = of the presently selected range |
Observed authority requirements
EMC | 2014/30/EU & UK SI 2016/1091 |
LVD | 2014/35/EU & UK SI 2016/1101 |
RoHS | 2011/65/EU & UK SI 2012/3032 |
EAC | TR-CU 020/2011 |
EAC LVD | TR-CU 004/2011 |
Approvals
c UL us, UL 508 | E231911 |
FM | 3025177 |
DNV Marine | TAA0000101 |
EU RO MR Type Approval | MRA000000Z |
SIL | Hardware assessed for use in SIL applications |