Description

PR 3117 Bipolar isolated converter

Application

  • The 3117 is an isolating converter which can be used for signal conversion of standard bipolar analog process signals into a unipolar analog signal.
  • The unit offers 3-port isolation and provides surge suppression and protects control systems from transients and noise.
  • The 3117 also eliminates ground loops and can be used for measuring floating signals.
  • Mounting of the 3117 can be in Safe area or in Zone 2 and Cl. 1 Div 2 area and is approved for marine applications.

Technical characteristics

  • Flexible 24 VDC (±30%) supply via power rail or connectors.
  • Excellent conversion accuracy, better than 0.05% of selected range.
  • Inputs and outputs are floating and galvanically separated.
  • A green front LED indicates operation status for the device.
  • All terminals are protected against overvoltage and polarity error.
  • Meeting the NAMUR NE21 recommendations, the 3117 ensures top measurement performance in harsh EMC environments.
  • High galvanic isolation of 2.5 kVAC.
  • Fast input to output response time < 7 ms / > 100 Hz – 10 Hz bandwidth damping possible via DIP-switch.
  • Excellent signal/noise ratio > 60 dB.

Mounting / installation / programming

  • Fast and easy configuration of factory calibrated measurement ranges via DIP-switches.
  • A very low power consumption allows DIN rail mounting without the need for any air gap.
  • Wide temperature operation range: -25…+70°C.

Environmental Conditions

Operating temperature-25°C to +70°C
Storage temperature-40°C to +85°C
Calibration temperature20…28°C
Relative humidity< 95% RH (non-cond.)
Protection degreeIP20
Installation inPollution degree 2 & meas. / overvoltage cat. II

Mechanical specifications

Dimensions (HxWxD)113 x 6.1 x 115 mm
Weight approx.70 g
DIN rail typeDIN EN 60715/35 mm
Wire size0.13…2.5 mm2 / AWG 26…12 stranded wire
Screw terminal torque0.5 Nm
VibrationIEC 60068-2-6
2…25 Hz±1.6 mm
25…100 Hz±4 g

Common specifications – PR 3117 Bipolar isolated converter

Supply

Supply voltage16.8…31.2 VDC
Max. required power0.80 W
Max. power dissipation0.43 W

Isolation voltage

Isolation voltage, test / working2.5 kVAC / 300 VAC (reinforced)
Zone 2 / Div. 2250 VAC

Response time

Response time (0…90%, 100…10%)< 7 ms or < 44 ms
MTBF, acc. to IEC 61709 (SN29500)> 241 years
Signal / noise ratioMin. 60 dB (0…100 kHz)
Signal dynamics, inputAnalog signal chain
Signal dynamics, outputAnalog signal chain
ProgrammingDIP-switches
Cut-off frequency (3 dB)> 100 Hz or 10 Hz (selectable via DIP-switch)
Accuracy< ±0.05% of span
Temperature coefficient< ±0.01% of span / °C
EMC immunity influence< ±0.5% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst< ±1% of span

Input specifications

Current input

Measurement range-23…+23 mA
Programmable measurement ranges± 10 and ± 20 mA
Input voltage drop< 1 VDC @ 23 mA

Voltage input

Measurement range-11.5…+11.5 V
Programmable ranges±5 and ±10 V
Input resistance≥ 1 MΩ

Output specifications – PR 3117 Bipolar isolated converter

Current output

Signal range0…23 mA
Programmable signal ranges0 / 4…20 mA
Load (@ current output)≤ 600 Ω
Load stability≤ 0.002% of span / 100 Ω
Current limit≤ 28 mA

Voltage output

Signal range0…10 VDC
Programmable signal ranges0/1…5 and 0/2…10 V
Load (@ voltage output)≥ 10 kΩ
of span= of the presently selected range

I.S. / Ex marking

ATEXII 3 G Ex ec IIC T4 Gc
IECExEx ec IIC T4 Gc
FM, USCl. I, Div. 2, Gp. A, B, C, D T4 or Cl. I, Zone 2, AEx nA IIC T4
FM, CACl. I, Div. 2, Gp. A, B, C, D T4 or Cl. I, Zone 2, Ex nA IIC T4

Observed authority requirements

EMC2014/30/EU & UK SI 2016/1091
LVD2014/35/EU & UK SI 2016/1101
ATEX2014/34/EU & UK SI 2016/1107
RoHS2011/65/EU & UK SI 2012/3032
EACTR-CU 020/2011
EAC ExTR-CU 012/2011

Approvals – PR 3117 Bipolar isolated converter

ATEXKEMA 10ATEX0147 X
IECExKEM 10.0068X
UKEXDEKRA 21UKEX0055X
c FM usFM17US0004X / FM17CA0003X
c UL us, UL 61010-1E314307
CCC2020322310003554
EAC ExEAEU KZ 7500361.01.01.08756
DNV MarineTAA00001RW