Description
Application
- Linearized, electronic temperature measurement with RTD or TC sensor.
- Conversion of linear resistance variation to a standard analog current / voltage signal, i.e. from solenoids and butterfly valves or linear movements with attached potentiometer.
- Power supply and signal isolator for 2-wire transmitters.
- Process control with standard analog output.
- Galvanic separation of analog signals and measurement of floating signals.
- Mount the device in Safe area or in Zone 2 and Cl. 1 Div 2. area.
Advanced features – PR 3114 Isolated universal converter
- When 3114 is used in combination with the 4501 display / programming front and ConfigMate 4590, all operational parameters can be modified to suit any application.
Technical characteristics
- A green / red front LED indicates normal operation and malfunction.
- 3-port 2.5 kVAC galvanic isolation.
Uses As:
Isolating Universal Converter 3114
Environmental Conditions
Operating temperature | -25°C to +70°C |
Storage temperature | -40°C to +85°C |
Calibration temperature | 20…28°C |
Relative humidity | < 95% RH (non-cond.) |
Protection degree | IP20 |
Installation in | Pollution degree 2 & meas. / overvoltage cat. II |
Mechanical specifications
Dimensions (HxWxD) | 113 x 6.1 x 115 mm |
Weight approx. | 70 g |
DIN rail type | DIN EN 60715/35 mm |
Wire size | 0.13…2.5 mm2 / AWG 26…12 stranded wire |
Screw terminal torque | 0.5 Nm |
Vibration | IEC 60068-2-6 |
2…25 Hz | ±1.6 mm |
25…100 Hz | ±4 g |
Common specifications – PR 3114 Isolated universal converter
Supply voltage | 16.8…31.2 VDC |
Fuse | 400 mA SB / 250 VAC |
Max. required power | ≤ 1.2 W |
Max. power dissipation | 0.65 W |
Isolation voltage, test / working | 2.5 kVAC / 300 VAC (reinforced) |
Zone 2 / Div. 2 | 250 VAC |
Temperature input (0…90%, 100…10%) | ≤ 1 s |
mA / V input (0…90%, 100…10%) | ≤ 400 ms |
Signal / noise ratio | Min. 60 dB (0…100 kHz) |
Signal dynamics, input | 24 bit |
Signal dynamics, output | 16 bit |
Programming | ConfigMate 4590 |
Accuracy | Better than 0.1% of sel. range |
EMC immunity influence | < ±0.5% of span |
Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% of span |
Input specifications – PR 3114 Isolated universal converter
RTD type | Pt10/20/50/100/200/250; Pt300/Pt400/500/1000; Ni50/100/120/1000 |
Cable resistance per wire | 50 Ω (max.) |
Sensor current | Nom. 0.2 mA |
Effect of sensor cable resistance (3-/4-wire) | < 0.002 Ω / Ω |
Sensor error detection | Yes |
Short circuit detection | < 15 Ω |
Linear resistance min….max. | 0 Ω…10000 Ω |
Potentiometer min….max. | 10 Ω…100 kΩ |
Thermocouple type | B, E, J, K, L, N, R, S, T, U, W3, W5, LR |
CJC via int. mounted sensor | ±(2.0°C + 0.4°C * Δt) |
Sensor error detection | Yes |
Sensor error current: When detecting / else | Nom. 2 μA / 0 μA |
Measurement range | 0…23 mA |
Programmable measurement ranges | 0…20 and 4…20 mA |
Input resistance | Nom. 20 Ω + PTC 50 Ω |
Measurement range | 0…12 VDC |
Programmable measurement ranges | 0/0.2…1, 0/1…5, 0/2…10 VDC |
Input resistance | Nom. 10 MΩ |
2-wire transmitter supply | > 15 V / 20 mA |
Output specifications – PR 3114 Isolated universal converter
Signal range | 0…23 mA |
Programmable signal ranges | 0…20/4…20/20…0/20…4 mA |
Load (@ current output) | ≤ 600 Ω |
Load stability | ≤ 0.01% of span / 100 Ω |
Sensor error indication | 0 / 3.5 / 23 mA / none |
NAMUR NE43 Upscale/Downscale | 23 mA / 3.5 mA |
Current limit | ≤ 28 mA |
Signal range | 0…10 VDC |
Programmable signal ranges | 0/0.2…1; 0/1…5 ; 0/2…10; 1…0.2/0; 5…1/0; 10…2/0 V |
Load (@ voltage output) | ≥ 10 kΩ |
of span | = of the presently selected range |
I.S. / Ex marking – PR 3114 Isolated universal converter
ATEX | II 3 G Ex ec IIC T4 Gc |
IECEx | Ex ec IIC T4 Gc |
FM, US | Cl. I, Div. 2, Gp. A, B, C, D T4 or Cl. I, Zone 2, AEx nA IIC T4 |
FM, CA | Cl. I, Div. 2, Gp. A, B, C, D T4 or Cl. I, Zone 2, Ex nA IIC T4 |
Observed authority requirements
EMC | 2014/30/EU & UK SI 2016/1091 |
LVD | 2014/35/EU & UK SI 2016/1101 |
ATEX | 2014/34/EU & UK SI 2016/1107 |
RoHS | 2011/65/EU & UK SI 2012/3032 |
EAC | TR-CU 020/2011 |
EAC Ex | TR-CU 012/2011 |
Approvals – PR 3114 Isolated universal converter
ATEX | KEMA 10ATEX0147 X |
IECEx | KEM 10.0068X |
UKEX | DEKRA 21UKEX0055X |
c FM us | FM17US0004X / FM17CA0003X |
c UL us, UL 61010-1 | E314307 |
CCC | 2020322310003554 |
EAC Ex | EAEU KZ 7500361.01.01.08756 |
DNV Marine | TAA00001RW |
Data sheet & Manuals – PR 3114 Isolated universal converter
PR 3114 Datasheet
PR 3114 Manuals