Description
3113 HART 7 Isolated Temperature Converter
Application
- The 3113 temperature converter measures a standard Pt100, TC J and K temperature sensor, and provides an isolated active analog current and HART signal output.
- High 3 port isolation provides surge suppression and protects the control system from transients and noise.
- The 3113 can be mounted in the safe area or in Zone 2 / Division 2 areas.
- Approved for marine applications.
Technical characteristics
- Flexibly powered by 24 VDC (±30%) via power rail or connectors.
- A 60 ms fast response time with simultaneous sensor error detection when selected.
- Selectable internal/external CJC.
- Excellent conversion accuracy in all available ranges, better than 0.05% of span.
- Meeting the NAMUR NE21 recommendations, the 3113 provides top measurement performance in harsh EMC environments.
- The device meets the NAMUR NE43 standard defining out of range and sensor error output values.
- A visible green LED indicates operational status of the unit and the input sensor.
- All terminals are protected against overvoltage and polarity error.
- High galvanic isolation of 2.5 kVAC.
- Excellent signal/noise ratio of > 60 dB.
Mounting / installation / programming
- Selectable HART mode with HART 7 revision protocol enables extended device programming.
- Selectable DIP-mode for easy configuration of more than 1000 factory calibrated measurement ranges with HART read only feature.
- Selectable HART-mode to enable full HART read-write capability.
- The narrow 6.1 mm housing allows up to 163 units to be mounted per meter of DIN rail, without any air gap between units.
- Wide ambient temperature range of -25…+70°C.
Data sheet & Manuals
Data sheet
Manuals
Environmental Conditions
Operating temperature | -25°C to +70°C |
Storage temperature | -40°C to +85°C |
Calibration temperature | 20…28°C |
Relative humidity | < 95% RH (non-cond.) |
Protection degree | IP20 |
Installation in | Pollution degree 2 & meas. / overvoltage cat. II |
Mechanical specifications
Dimensions (HxWxD) | 113 x 6.1 x 115 mm |
Weight approx. | 70 g |
DIN rail type | DIN EN 60715/35 mm |
Wire size | 0.13…2.5 mm2 / AWG 26…12 stranded wire |
Screw terminal torque | 0.5 Nm |
Vibration | IEC 60068-2-6 |
2…25 Hz | ±1.6 mm |
25…100 Hz | ±4 g |
Common specifications
Supply | |
Supply voltage | 16.8…31.2 VDC |
Max. required power | 0.70 W |
Max. power dissipation | 0.70 W |
Isolation voltage | |
Isolation voltage, test / working | 2.5 kVAC / 300 VAC (reinforced) |
Zone 2 / Div. 2 | 250 VAC |
Response time | |
HART mode, (0…90%, 100…10%) | 60 ms…60 s, programmable |
DIP mode, (0…90%, 100…10%) | < 60 ms |
Accuracy | Better than 0.05% of selected range |
Signal / noise ratio | Min. 60 dB |
Long-term stability, better than | ±0.1% of span / year (±0.3% of span / 5 years) |
Programming | DIP-switches |
Signal dynamics, input | 23 bit |
Signal dynamics, output | 18 bit |
EMC immunity influence | < ±0.5% of span |
Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% of span |
Incorrect DIP-switch setting identification | 3.5 mA output; LED 0.5 s / 1 Hz |
Input specifications
RTD input | |
Temperature range, Pt100 | -200…+850°C |
Min. measurement range (span) | 10°C |
Accuracy: the greater of | Better than 0.05% of span or 0.1°C |
Temperature coefficient: the greater of | 0.02°C/°C or ≤ ±0.01%/°C |
Sensor current | < 150 µA |
Sensor cable resistance | < 50 Ω per wire |
Effect of sensor cable resistance (3-/4-wire) | < 0.002 Ω / Ω |
Sensor error detection | Yes – selectable via DIP-switch |
Broken sensor detection | > 800 Ω |
Shorted sensor detection | < 18 Ω |
TC input | |
Temperature range, TC J | -100…+1200°C |
Temperature range, TC K | -180…+1372°C |
Min. measurement range (span) – TC J & K | 50°C |
Accuracy: the greater of | Better than 0.05% of span or 0.5°C |
Temperature coefficient: the greater of | 0.1°C/°C or ≤ ±0.01%/°C |
Sensor cable resistance | < 5 kΩ per wire |
Cold junction compensation (CJC): Accuracy @ external Pt100 input | Better than ±0.15°C |
Cold junction compensation (CJC): Accuracy @ internal CJC | Better than ±2.5°C |
Internal CJC error detection | Yes |
External CJC error detection | Yes – selectable via DIP-switch |
Open Thermocouple detection | Yes – selectable via DIP-switch |
Output specifications
Common output specifications | |
Updating time | 10 ms |
Current output | |
Signal range | 0…23 mA |
Programmable signal ranges | 4…20 and 20…4 mA |
Load (@ current output) | ≤ 600 Ω |
Load stability | ≤ 0.01% of span / 100 Ω |
Sensor error indication | 3.5 mA or 23 mA / acc. to NAMUR NE43 or OFF |
Open output | < 20 V |
HART protocol revisions | HART 7 |
I.S. / Ex marking
ATEX | II 3 G Ex ec IIC T4 Gc |
IECEx | Ex ec IIC T4 Gc |
FM, US | Cl. I, Div. 2, Gp. A, B, C, D T4 or Cl. I, Zone 2, AEx nA IIC T4 |
FM, CA | Cl. I, Div. 2, Gp. A, B, C, D T4 or Cl. I, Zone 2, Ex nA IIC T4 |
EAC Ex | 2Ex nA IIC T4 Gc X |
Observed authority requirements
EMC | 2014/30/EU & UK SI 2016/1091 |
LVD | 2014/35/EU & UK SI 2016/1101 |
ATEX | 2014/34/EU & UK SI 2016/1107 |
RoHS | 2011/65/EU & UK SI 2012/3032 |
EAC | TR-CU 020/2011 |
EAC Ex | TR-CU 012/2011 |
Approvals
ATEX | KEMA 10ATEX0147 X |
IECEx | KEM 10.0068X |
UKEX | DEKRA 21UKEX0055X |
c FM us | FM17US0004X / FM17CA0003X |
c UL us, UL 61010-1 | E314307 |
EAC Ex | EAEU KZ 7500361.01.01.08756 |
DNV Marine | TAA00001RW |
Advanced Temperature Signal Conversion with PR Electronics
The 3113 HART 7 Isolated Temperature Converter by PR Electronics is a cutting-edge solution for precise and reliable temperature signal conversion. With HART 7 communication and galvanic isolation, this converter ensures seamless integration into industrial control systems while maintaining high accuracy and stability.
Key Features and Benefits
- HART 7 Protocol Compatibility – Enables remote configuration, diagnostics, and improved communication efficiency.
- High-Accuracy Temperature Conversion – Supports RTDs, thermocouples, resistance, and voltage inputs.
- Galvanic Isolation – Protects against ground loops and electrical interference for superior signal integrity.
- Loop-Powered (2-Wire Design) – Reduces wiring complexity and enhances energy efficiency.
- Compact & Robust Industrial Design – Suitable for harsh environments with high resistance to electrical noise and extreme conditions.
Why Choose PR Electronics?
PR Electronics is a global leader in industrial signal conditioning, offering innovative temperature converters that ensure precision and reliability. The 3113 HART 7 Isolated Temperature Converter is engineered for optimal performance in process automation and industrial applications, making it the perfect choice for demanding industries.
Applications
- Process Automation
- Power Generation
- Food & Beverage Industry
- Chemical & Pharmaceutical Processing
- HVAC & Environmental Monitoring
Get Started Today
Enhance your temperature measurement system with the PR Electronics 3113 HART 7 Isolated Temperature Converter. Contact us today for more information or to discuss a customized solution for your industry needs.