Description
Application
- Isolation and conversion of standard DC signals.
- Galvanic separation of analog current and voltage signals.
- Elimination of ground loops and measurement of floating signals.
- A competitive choice in terms of both price and technology for galvanic isolation of current and voltage signals to SCADA systems or PLC equipment.
- Installation in ATEX Ex zone 2 / IECEx zone 2 / FM division 2.
- Suitable for environments with high vibration stress, e.g. ships.
Technical characteristics – PR 3109 Isolated converter splitter
- Easy configuration via DIP-switches.
- The input is protected against overvoltage and polarity error.
- Factory-calibrated measurement ranges.
- Inputs and outputs are floating and galvanically separated.
Need support to select the right product for your application?
Our sales engineers are ready to help specify the right device to meet your needs.
Reach out by phone to get in touch with us straight away – or use the contact form or quick quote function to send your RFQ directly from the website. You’ll get a response within 24 hours on normal business days. You can expect to get a confirmed delivery date via email within 2 days after we have received your order. As soon as your package leaves our warehouse, you’ll receive tracking details via email. And if you have any questions along the way we’re just a phone call or email away.
Environmental Conditions
Operating temperature | -25°C to +70°C |
Storage temperature | -40°C to +85°C |
Calibration temperature | 20…28°C |
Relative humidity | < 95% RH (non-cond.) |
Protection degree | IP20 |
Installation in | Pollution degree 2 & meas. / overvoltage cat. II |
Mechanical specifications
Dimensions (HxWxD) | 113 x 6.1 x 115 mm |
Weight approx. | 70 g |
DIN rail type | DIN EN 60715/35 mm |
Wire size | 0.13…2.5 mm2 / AWG 26…12 stranded wire |
Screw terminal torque | 0.5 Nm |
Vibration | IEC 60068-2-6 |
2…25 Hz | ±1.6 mm |
25…100 Hz | ±4 g |
Common specifications – PR 3109 Isolated converter splitter
Supply voltage | 16.8…31.2 VDC |
Max. required power | ≤ 1.2 W |
Max. power dissipation | 0.60 W |
Isolation voltage, test / working | 2.5 kVAC / 300 VAC (reinforced) |
Zone 2 / Div. 2 | 250 VAC |
Response time (0…90%, 100…10%) | < 7 ms |
Programming | DIP-switches |
Signal / noise ratio | > 60 dB |
Cut-off frequency (3 dB) | > 100 Hz |
Signal dynamics, input | Analog signal chain |
Signal dynamics, output | Analog signal chain |
Accuracy | Better than 0.05% of selected range |
Temperature coefficient | < ±0.01% of span / °C |
EMC immunity influence | < ±0.5% of span |
Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% of span |
Input specifications – PR 3109 Isolated converter splitter
Measurement range | 0…23 mA |
Programmable measurement ranges | 0…20 and 4…20 mA |
Input voltage drop | < 1.5 VDC |
Input resistance | Nom. 20 Ω + PTC 50 Ω |
Measurement range | 0…10.25 V 0…11.5 V / 0…5.75 V
|
Programmable measurement ranges | 0/1…5 and 0/2…10 V |
Input resistance | ≥ 500 kΩ |
2-wire transmitter supply | > 17 V / 20 mA |
Output specifications – PR 3109 Isolated converter splitter
Signal range | 0…23 mA |
Programmable signal ranges | 0 / 4…20 mA |
Load (@ current output) | ≤ 300 Ω |
Load stability | ≤ 0.002% of span / 100 Ω |
Current limit | ≤ 28 mA |
Signal range | 0…10 VDC |
Programmable signal ranges | 0/1…5 and 0/2…10 V |
Load (@ voltage output) | ≥ 10 kΩ |
of span | = of the DIP switch selected output range |
I.S. / Ex marking – PR 3109 Isolated converter splitter
ATEX | II 3 G Ex ec IIC T4 Gc |
IECEx | Ex ec IIC T4 Gc |
FM, US | Cl. I, Div. 2, Gp. A, B, C, D T4 or Cl. I, Zone 2, AEx nA IIC T4 |
FM, CA | Cl. I, Div. 2, Gp. A, B, C, D T4 or Cl. I, Zone 2, Ex nA IIC T4 |
Observed authority requirements
EMC | 2014/30/EU & UK SI 2016/1091 |
LVD | 2014/35/EU & UK SI 2016/1101 |
ATEX | 2014/34/EU & UK SI 2016/1107 |
RoHS | 2011/65/EU & UK SI 2012/3032 |
EAC | TR-CU 020/2011 |
EAC Ex | TR-CU 012/2011 |
Approvals – PR 3109 Isolated converter splitter
ATEX | KEMA 10ATEX0147 X |
IECEx | KEM 10.0068X |
UKEX | DEKRA 21UKEX0055X |
c FM us | FM17US0004X / FM17CA0003X |
c UL us, UL 61010-1 | E314307 |
CCC | 2020322310003554 |
EAC Ex | EAEU KZ 7500361.01.01.08756 |
DNV Marine | TAA00001RW |
Data sheet & Manuals – PR 3109 Isolated converter splitter