Description

PR 3108 Isolated repeater splitter

Application

  • Isolation and conversion of standard DC signals.
  • Galvanic separation of analog current signals.
  • Elimination of ground loops and measurement of floating signals.
  • A competitive choice in terms of both price and technology for galvanic isolation of current signals to SCADA systems or PLC equipment.
  • Installation in ATEX Ex zone 2 / IECEx Zone 2 / FM division 2.
  • Suitable for environments with high vibration stress, e.g. ships.

Technical characteristics

  • The input is protected against overvoltage and polarity error.
  • Factory-calibrated measurement ranges.
  • Inputs and outputs are floating and galvanically separated.

Environmental Conditions – PR 3108 Isolated repeater splitter

Operating temperature-25°C to +70°C
Storage temperature-40°C to +85°C
Calibration temperature20…28°C
Relative humidity< 95% RH (non-cond.)
Protection degreeIP20
Installation inPollution degree 2 & meas. / overvoltage cat. II

Mechanical specifications

Dimensions (HxWxD)113 x 6.1 x 115 mm
Weight approx.70 g
DIN rail typeDIN EN 60715/35 mm
Wire size0.13…2.5 mm2 / AWG 26…12 stranded wire
Screw terminal torque0.5 Nm
VibrationIEC 60068-2-6
2…25 Hz±1.6 mm
25…100 Hz±4 g

Common specifications – PR 3108 Isolated repeater splitter

Supply

Supply voltage16.8…31.2 VDC
Max. required power0.75 W
Max. power dissipation0.48 W

Isolation voltage

Isolation voltage, test / working2.5 kVAC / 300 VAC (reinforced)
Zone 2 / Div. 2250 VAC

Response time

Response time (0…90%, 100…10%)< 7 ms
Signal / noise ratio> 60 dB
Cut-off frequency (3 dB)> 100 Hz
Signal dynamics, inputAnalog signal chain
Signal dynamics, outputAnalog signal chain
AccuracyBetter than 0.05%
Temperature coefficient< ±0.01% of span / °C
EMC immunity influence< ±0.5% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst< ±1% of span

Input specifications – PR 3108 Isolated repeater splitter

Current input

Measurement range0…23 mA
Input voltage drop< 1.5 VDC
Input resistanceNom. 20 Ω + PTC 50 Ω

Output specifications – PR 3108 Isolated repeater splitter

Current output

Signal range0…23 mA
Load (@ current output)≤ 300 Ω
Load stability≤ 0.002% of span / 100 Ω
Current limit≤ 28 mA
of span= 0…20 mA

I.S. / Ex marking

ATEXII 3 G Ex ec IIC T4 Gc
IECExEx ec IIC T4 Gc
FM, USCl. I, Div. 2, Gp. A, B, C, D T4 or Cl. I, Zone 2, AEx nA IIC T4
FM, CACl. I, Div. 2, Gp. A, B, C, D T4 or Cl. I, Zone 2, Ex nA IIC T4

Observed authority requirements

EMC2014/30/EU & UK SI 2016/1091
LVD2014/35/EU & UK SI 2016/1101
ATEX2014/34/EU & UK SI 2016/1107
RoHS2011/65/EU & UK SI 2012/3032
EACTR-CU 020/2011
EAC ExTR-CU 012/2011

Approvals – PR 3108 Isolated repeater splitter

ATEXKEMA 10ATEX0147 X
IECExKEM 10.0068X
UKEXDEKRA 21UKEX0055X
c FM usFM17US0004X / FM17CA0003X
c UL us, UL 61010-1E314307
CCC2020322310003554
EAC ExEAEU KZ 7500361.01.01.08756
DNV MarineTAA00001RW

Data sheet & Manuals – PR 3108 Isolated repeater splitter


PR 3108 Datasheet

PR 3108 Manuals

———————————————————————————————–

Thinking of any other product? or

Need support to select the right product for your application?

Our sales engineers are ready to help specify the right device to meet your needs.

Reach out by phone to get in touch with us straight away – or use the contact form or quick quote function to send your RFQ directly from the website. You’ll get a response within 24 hours on normal business days. You can expect to get a confirmed delivery date via email within 2 days after we have received your order. As soon as your package leaves our warehouse, you’ll receive tracking details via email. And if you have any questions along the way we’re just a phone call or email away.

Additional information

Weight0.5 kg