Description
3105 Isolated converter
Application
- Isolation and conversion of standard DC signals.
- Galvanic separation of analog current and voltage signals.
- Elimination of ground loops and measurement of floating signals.
- A competitive choice in terms of both price and technology for galvanic isolation of current and voltage signals to SCADA systems or PLC equipment.
- Suitable for environments with high vibration stress, e.g. ships.
Technical characteristics
- Easy configuration via DIP-switches.
- The input is protected against overvoltage and polarity error.
- Factory-calibrated measurement ranges.
- Inputs and outputs are floating and galvanically separated.
Data sheet & Manuals
Data sheet
Manuals
Environmental Conditions
Operating temperature | 0°C to +70°C |
Storage temperature | -40°C to +85°C |
Calibration temperature | 20…28°C |
Relative humidity | < 95% RH (non-cond.) |
Protection degree | IP20 |
Installation in | Pollution degree 2 & meas. / overvoltage cat. II |
Mechanical specifications
Dimensions (HxWxD) | 113 x 6.1 x 115 mm |
Weight approx. | 70 g |
DIN rail type | DIN EN 60715/35 mm |
Wire size | 0.13…2.5 mm2 / AWG 26…12 stranded wire |
Screw terminal torque | 0.5 Nm |
Vibration | IEC 60068-2-6 |
2…25 Hz | ±1.6 mm |
25…100 Hz | ±4 g |
Common specifications
Supply | |
Supply voltage | 16.8…31.2 VDC |
Max. required power | 0.80 W |
Max. power dissipation | 0.52 W |
Isolation voltage | |
Isolation voltage, test / working | 2.5 kVAC / 300 VAC (reinforced) |
Response time | |
Response time (0…90%, 100…10%) | < 7 ms |
Programming | DIP-switches |
Signal / noise ratio | > 60 dB |
Cut-off frequency (3 dB) | > 100 Hz |
Signal dynamics, input | Analog signal chain |
Signal dynamics, output | Analog signal chain |
Accuracy | Better than 0.2% of selected range |
Temperature coefficient | < ±0.015% of span / ˚C |
EMC immunity influence | < ±0.5% of span |
Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% of span |
Input specifications
Current input | |
Measurement range | 0…23 mA |
Programmable measurement ranges | 0…20 and 4…20 mA |
Input voltage drop | < 1.5 VDC |
Input resistance | Nom. 20 Ω + PTC 50 Ω |
Voltage input | |
Measurement range | 0…10.25 V 0…11.5 V / 0…5.75 V |
Programmable measurement ranges | 0/1…5 and 0/2…10 V |
Input resistance | ≥ 500 kΩ |
Output specifications
Current output | |
Signal range | 0…23 mA |
Programmable signal ranges | 0 / 4…20 mA |
Load (@ current output) | ≤ 600 Ω |
Load stability | ≤ 0.002% of span / 100 Ω |
Current limit | ≤ 28 mA |
Voltage output | |
Signal range | 0…10 VDC |
Programmable signal ranges | 0/1…5 and 0/2…10 V |
Load (@ voltage output) | ≥ 10 kΩ |
of span | = of the DIP switch selected output range |
Observed authority requirements
EMC | 2014/30/EU & UK SI 2016/1091 |
LVD | 2014/35/EU & UK SI 2016/1101 |
RoHS | 2011/65/EU & UK SI 2012/3032 |
EAC | TR-CU 020/2011 |
Approvals
c UL us, UL 61010-1 | E314307 |
DNV Marine | TAA00001RW |
The 3105 Isolated Converter by PR Electronics is a high-performance solution designed to ensure accurate and reliable signal conversion in industrial applications. With superior electrical isolation, this converter enhances signal integrity and protects your control systems from interference and ground loops.
Key Features and Benefits
- High-Performance Isolation – Provides galvanic isolation between input, output, and power supply.
- Universal Signal Conversion – Supports a wide range of analog signal types, including current and voltage.
- Compact and Robust Design – Ideal for space-limited installations in harsh industrial environments.
- Low Power Consumption – Enhances energy efficiency while maintaining high performance.
- Easy Configuration – Simple setup with user-friendly calibration options.
Why Choose PR Electronics?
PR Electronics is a global leader in industrial signal conditioning, offering innovative and reliable solutions for process automation. The 3105 Isolated Converter is engineered to improve signal quality, reduce noise, and ensure seamless integration into industrial control systems.
Applications
- Process Automation
- Industrial Control Systems
- Power Generation
- Chemical & Pharmaceutical Industries
- Factory Automation
Get Started Today
Enhance your signal conversion with the PR Electronics 3105 Isolated Converter. Contact us today for more information or to discuss a customized solution tailored to your industry needs.